Zs. J6ZSA

Department of Building Materials Technical University, H-1521 Budapest

Received March 30, 1989 Presented by Prof. Dr. Gy. Balazs

Ahstract

The mechanic, thermomechanic, deflection and moisture properties of aerated concrete wall elements (GM 500/2) that have been in production since 1986 were inyestigated. The main causes of cracks appearing shortly after construction were: the inhomogeneous strength and modulus of elasticity depending on moisture distribution, the inhomogeneous and not "custom designed" other structural elements (slabs, beams), the yery high strength of the applied mortar and inaccuracy in the attachment of element rows.

1. Introduction

The ~IATRA Aerated Concrete Factory of KOSZIG company has been producing aerated concrete blocks using Hebel's technology since 1986. The raw material is fly ash from a nearby lignit burning power station, the binders are lime and cement, the aerator agent is aluminium paste. The present article summarizes the findings of a test program of the GM 500/2 gas concrete ele- ment.

2. The tested properties

The dry body density is usually 30-70 kg(m31ess than the nominal value of 500 kg/m3 • The internal density distribution of the element depends on its position during the manufacturing procedure. The elements in the middle of the vat usually have homogeneous density, while elements manufactured around the edges of the vat are more likely to be inhomogeneous. (See Fig- ures 1 and 2).

The moisture content of the elements after manufacturing is about 40-45 m %, this gives around 650 kg/m3 body density for calculations.

The compressive strength tested according to the appropriate Hungarian Standard (3 cubes, 100 X 100 X 100 mm3 , dried at 105 °C, load direction - as if it was built in a wall structure) gave results above 2 MPa - the required strength according to the Hungarian Standard. If samples are taken out of one element strength results may differ as a result of inhomogeneous density and the faults of a porous system. Wet or soaked samples have 20-40% lower strength compared to dry ones.

3

(2)

34 ZS. J6ZSA

It was stated after the complex strength tests of 150 X 150 X 600 mm3 samples that flexure strength - loading at every third of the beam of 500 mm span - was 10-15% of the compressive strength, the compressed area was 150 X 150 mm2Splitting tests, using two 20 mm diameter steel bars, resulted in around 6-8% of the compressive strength. The strength loss caused by water content was significant in this case also.

0 ,

~I

46~,4

-i.67f5 464ik /1

19 i ----[ 6 452 7 455 8 454,9 46210 4581 m3j

····.11 45112 455:13 458:14 458:15 456, '

--'-:1~

453i17 454i18 460:19 459@0 4541 I

- . - J , f - - . - - - -f:JX) - - - ; -

~ ~--~.--. . ~--.---~-~

400 ~--~---.. +--.--.- .. ---

Fig. 1. The change in body density of element cast in the middle of the "at. (20 samples, 100 100 >< 100 mm3 cubes)

Testing the strength according to DIN showed that elements cracked' under minor load as a result of drying and non-uniform deflection. Strengthen- ing of aerated concrete is insignificant after manufacturing and strength basically depends on its body density.

The limit stress (0.7MPa) for design should be reconsidered to he 0.6 }IPa, furthermore, for low density (420-430 kg/m3) elements 0 .. 3 ::\IPa 'would he a wise stress limit.

Testing of chemical components and derivatograms showed that aerated concrete had yery little free lime and that increases the corrosion danger.

Durability tests were carried out to find out the effects of climate (e.g.

CO2, S02' smoke and coal tar), 'water, oil stains and winter salting (chlorides).

Possihle structural changes or strength loss v{ere investigated.

(3)

""

o LD N

E

.,-

---.-.=====--==--=====-~----==-!

, ,1 472'2 46013 443!443515 415i

kg

,!

---- 6 471 i7 465i8 441i9 426i'0422Im3!

11 464 112 45113 441 :14 428115 4301 i

__ 469'1~~_18 441r9 432120430\ !

,;. ,---.---~

,;'--._--_.--- 600-·-- _ ... -.. _---{-

5CO

I

I I

~ "»>",G\

I "'';;<''~

'~r -

I

I I

I I I

400

Fig. 2. The change in body density of element cast on the edge of the vat. (20 samples, 100' X 100 X 100 mm3 cubes) ~

3-3.5 month long tests sho-wed that CaO may leave the aerated concrete thus further reducing the small free lime content. Coal tar treated wet samples showed significant strength loss.

As a result of ahsorption and desorption tests the ahsorption saturation

"was found to be around 20-25% (depending on body density) and the equilib- rium moisture content was around 5-8 m%. (Figure 3).

The ch'ying of aerated concrete depended on the initial moisture content at 20 QC temperature achieved equilibrium during a one year period. (Figure 4).

(Sample surfaces were free in all directiom.) Built-in elements have only 37%

of total surface free thus drying takes even longer. The mortar on walls plus the real temperature and moisture effects ensure that drying takes almost 5-6 years.

The absorption rate of water saturated elements -was bet,\'een 42-50 V%

with high deyiation.

Frost-tha'w tests in 1986 showed 50% strength loss aftcr Ei cycles.

The Young-modulus of aerated concrete is largely influenced hy test methods and moisture content. The dry Young-modulus computed after the deflection of samples 'was marginally lo'wer (520-938 MPa) than factory speci- fications (1250 MPa). Tests according to DIN 1048 resulted in 1226-BSI ~IPa.

3*

(4)

36

20

~ 15 o E

ZS. J6ZSA

I I

I I I

I

!I

I ..:. 1

/~/ V

I

1

~i

i,

i

i I /.

I i 1

~I I

I

I i I

T I

I

I I

I i

! ! i

10 20 30 40 5q 60 70 80 90 100

Vapour content, v (0/0)

Fig. 3. The absorption and desorption isotherms of gas concrete

J

501

40

.

;;-

'" 30

'"

cs E

10 ----F14 -F15

3 7

I I 11

Ilj

, I, I

, i'

I' it 20

I

I'

I I1

I

L

I II

! 11 I I '15

I III

I I

i

i!

1"<\ III

\Ij

I >1'

I I

I il

I

, I !

I 11114

5 10

14 2633 47 96 130 19 age(day}

Fig. 4. Changing moisture content in a wall element

(5)

The deviation of results was very high. For moisture "softened" aerated concrete the Young-modulus was lower, although fully saturated samples showed increased Young-modulus.

Aerated concrete also has a significant shrinkage - 0.52-0.75% bet- ween 15-140 days measured along the direction of swelling after the natural drying procedure. (The moisture content was still around 14-15 m %, thus drying was not finished.) Until the 15th day the shrinkage was around 0.4%

according to El\U (Construction Quality Control Institution). One of the consequences of shrinkage was the "curving" of the elements. Swelling of an air dry element after 42 days in a water bath was 1.15%.

The factor of thermal expansion of aerated concrete depends on casting.

1986 tests gave 7.9 X 1Q-61/oC for dry and 7.2 X 10-6 l/oC for wet samples.

1987 tests gave 6.2 X 10-6 11°C longitudinally and 4-4.6 X 10-6 11°C in the traverse direction. Thermal expansion was thus direction dependent and lower than factory parameters (8 X 10-6 1/°C).

The vapour diffusion factors of samples made in 1986 were between 0.028 X 10-9 - 0.038 X 10-9 kg!~ X Pa X m. This depended on body density and porous distribution.

The thermal conductivity of dry aerated concrete samples was around O.13W/m K depending on the body density. Moisture increased thermal con- ductivity up to 0.25 \\"/m K.

Wall elements are rather big at 250 X 300 X 600 mm3 and their "fresh"

mass is around 30 kg. Construction is fast and efficient although lifting heavy elements over higher levels is tiring work and elements are frequently damaged.

3. Cause of cracks in wall structures

WaIls built from aerated concrete blocks are usually cracked in Hun- gary. The causes of cracks are listed below:

- Inhomogeneous body density and strength inside the elements.

- Inhomogeneous moisture content in the wall (dry edges, wet middle) also means strength difference and change of Young-modulus through the wall.

Low flexure and split strength and moisture reduces them further.

A significant 1 % shrinkage during drying (or swelling when moisture content increases) and inhomogeneous moisture content causes internal

stress~s.

Creep under permanent load and the inhomogeneous deflection be- cause of non-uniform body density, moisture content and strength qualities.

- Some structural parts are not "custom made" for this technology, e.g. ring beams, slabs etc. (Inhomogeneous structure with different deformation properties plus additional moisture into aerated concrete, e.g. casting ring beam.)

(6)

38 ZS. J6ZSA

Deformation because of temperature change.

Impeded deflections caused stresses from the very high strength of binding mortar.

- Large element size - high stresses from the previously mentioned impeded deflections.

- Inaccurate placement of elements especially when the top of each layer of elements was not properly flattened.

- Faulty construction practices.

Dr. Zsuzsanna J6ZSA H-1521, Budapest

Hivatkozások

KAPCSOLÓDÓ DOKUMENTUMOK

In the third media group – the Latvian printed press - the most (26) cases of possible hidden Advertising were identified in the newspaper “Rigas Balss” (The Voice

To compare the biomechanical properties of the specimens, the following four parameters were used: Young modulus of elasticity, maximum load, strain at tensile strength and strain at

Tensile strength and elongation at the maximum force (a), breaking strength and elongation at break (b), Young’s modulus and Charpy impact strength (c) in PET/PLA blends depending

Major research areas of the Faculty include museums as new places for adult learning, development of the profession of adult educators, second chance schooling, guidance

The decision on which direction to take lies entirely on the researcher, though it may be strongly influenced by the other components of the research project, such as the

Besides the accurate and consistent estimation of shortening due to creep, shrinkage and time changes of characteristic compressive strength and the modulus of elasticity,

The e ff ects of steel fiber strength on the mechanical properties of steel fiber reinforced concretes, such as compressive strength, modulus of elasticity, splitting tensile

3.3 Moisture susceptibility determination of HMA Indirect tensile strength test (AASHTO T283) [31] and resilient modulus (ASTM D7369) [32] determine the HMA