Ŕ periodica polytechnica

Mechanical Engineering 52/2 (2008) 61–66 doi: 10.3311/pp.me.2008-2.04 web: http://www.pp.bme.hu/me c Periodica Polytechnica 2008 RESEARCH ARTICLE

Analysis of energy consumption of air handling units based on probability theory

LászlóKajtár/MiklósKassai

Received 2008-01-18

Abstract

The existing building stock in Hungary accounts for over 40% of total energy consumption of which heating and air- conditioning systems use represents the most. International and national regulations encourage cutting down the energy con- sumption in buildings. For this reason it is important to de- termine energy consumption exactly. In view of outdoor air pa- rameters (temperature, humidity and enthalpy) variation a new calculation method was necessary to set up for evaluating of en- ergy consumption of air handling units. In consideration of the fact that outdoor air condition values can be regarded as a prob- ability variable we have worked out a new evaluation method of energy consumption of air handling units based on probability theory. The research work was carried out by scientific methods.

Keywords

Air handling units·energy consumption·probability theory

László Kajtár

Department of Building Service Engineering and Process Engineering, BME, H-1111 Budapest, Bertalan Lajos street 4-6, Hungary

e-mail: kajtar@epgep.bme.hu

Miklós Kassai

Department of Building Service Engineering and Process Engineering, BME, H-1111 Budapest, Bertalan Lajos street 4-6, Hungary

e-mail: kas.miklos@gmail.com

1 Introduction

The Directive 2002/91/EC of the European Parliament and Council on energy efficiency of buildings ordered to verify en- ergy consumption of buildings, to cut down and certify the en- ergy performance of buildings. Energy consumption of build- ings depends on the HVAC systems to a higher degree such as air-conditioning systems.

7/2006. (V.24.) TNM order offers a direction about deter- mination of energy consumption of the building and HVAC sys- tems in Hungary. It provides a solution to determine energy con- sumption of HVAC systems during the year. This procedure is suitable to calculate annual energy consumption of heating and ventilating systems but in consequence of size limits determina- tion of energy consumption of air-conditioning systems and air handling units have not ranged at large.

The aim of our research work was to work out a particular procedure. As outdoor air parameters (temperature, humidity and enthalpy) vary in daily and season period so vary the perfor- mance of heating, cooling and adiabatic humidifier constantly in the air handling unit [1]. The new scientific method that has been developed at Department of Building Service Engineering and Process Engineering in Budapest University of Technology and Economics considers outdoor climatic parameters (temper- ature, humidity, enthalpy) as probability variables [2]. Variation of outdoor air parameters were considered on the basis of dis- tribution function of outdoor air temperature and enthalpy. The new physical and mathematical model takes into account the air handling processes during the operation of air handling units [3,4]. In order to put into practise the mathematical method a computer program was made to carry out a quick and exact cal- culation.

2 Outdoor air condition as a probability variable From the perspective of air conditioning technology the key attributes of outdoor air are temperature, humidity and enthalpy.

These values randomly vary from minute to minute. The prob- ability theory starts from the bulk of the elementary results of some experiments (e.g.: air temperature measurement). One single real number can be attributed to each elementary event

Analysis of energy consumption of air handling units based on probability theory 2008 52 2 61

(2)

(the measured temperature). The correlation interpreted with this attribution is called the probability variable. We can talk about discrete and continuous distribution probability variable.

The air condition values can take any value within a range and may be regarded as a continuous probability variable. A proba- bility variable may have an expected value, dispersion, distribu- tion and density function.

A probability variable with a continuous distribution is char- acterized by the distribution (F(x)) and density (f(x)) func- tions.

The probability that the value of probability variable is be- tweenaandb:

P(a<x<b)=

b

Z

a

f(x)d x (1)

The distribution function shows the probability oft probability variable taking a value less thanx:

F(x)= P(t <x) (2) The distribution functions of outdoor air parameters (tempera- ture, enthalpy) can be applied for determine the actual energy consumption of air handling units [5]. The temperature, hu- midity and enthalpy of outdoor air can be accounted continuous distribution probability variable that can be converged as Gauss distribution [6].

Calculation of heating energy consumption it is necessary to take account of variation of outdoor air parameters (tempera- ture, humidity and enthalpy) that vary in daily and season pe- riod [7, 8]. Making energy calculation of a building, the outdoor air condition values can be regarded as a probability variable [9] that has momentary, maximum, minimum and average val- ues, distribution function which can be defined according daily, weekly, monthly and annual period. We can make more refine- ments by define a daytime period (07-19 hours) and a continuous operation (0-24 hours) of air handling units. Two distribution functions are shown in Fig. 1 and Fig. 2, in that a daytime (07- 19 hours) period and nightly period (19-07 hours) can be seen.

Any point of functions shows the hours and the percentage of the term when temperature or enthalpy of outdoor air was lower than the examined point. It follows that theτt otterm which con- cerns to the 100% distribution is equal to the reference period.

By integral calculation the air handling process is taken into ac- count in Mollier enthalpy chart.

Integral always can be calculated by the area under the func- tions during determination of cooling and heating energy con- sumption. In view of annual energy consumption operational costs can be calculated by knowledge of power and heat cost.

3 The physical and mathematical model

An air handling unit contains two main groups of elements:

supply and exhaust units. The main parts of an air handling unit:

filter, heat recovery unit, pre-heater, re-heater, cooler, by-pass,

The distribution functions of outdoor air parameters (temperature, enthalpy) can be applied for determine the actual energy consumption of air handling units [5]. The temperature, humidity and enthalpy of outdoor air can be accounted continuous distribution probability variable that can be converged as Gauss distribution [6].

Calculation of heating energy consumption it is necessary to take account of variation of outdoor air parameters (temperature, humidity and enthalpy) that vary in daily and season period [7,8]. Making energy calculation of a building, the outdoor air condition values can be regarded as a probability variable [9] that has momentary, maximum, minimum and average values, distribution function which can be defined according daily, weekly, monthly and annual period. We can make more refinements by define a daytime period (07-19 hours) and a continuous operation (0-24 hours) of air handling units. Two distribution functions are shown in Fig. 1. and Fig. 2., in that a daytime (07-19 hours) period and nightly period (19-07 hours) can be seen. Any point of functions shows the hours and the percentage of the term when temperature or enthalpy of outdoor air was lower than the examined point. It follows that the τtot term which concern to the 100%

distribution is equal to the reference period. By integral calculation the air handling process is taken into account in Mollier enthalpy chart.

Integral always can be calculated by the area under the functions during determination of cooling and heating energy consumption. In view of annual energy consumption operational costs can be calculated by knowledge of power and heat cost.

0 2 4 6 8 10 12 14 16 18 20 22 24 372

300

200

100

0

0 10 20 30 40 50 60 70 80 90 100 0 10 20 30 40 50 60 70 80 90 100

τ

, h

i , kcal/kgo

Distribution ,F, %

19...22

15...19 13...16 07...19 10...13

07...19 hrs 19...07 hrs 07...10 04...07

01...04 19...07

22...01

10...13

07...19 a, b,

i , kcal/kg

Fig. 1.The distribution function of outdoor air enthalpy in June (Budapest, average of measured temperatures between 1964-1972) [10]

Fig. 1. The distribution function of outdoor air enthalpy in June (Budapest, average of measured temperatures between 1964-1972) [10]

0 2 4 6 8 10 12 14 16 18 20 22 24

500

0

0 10 20 30 40 50 60 70 80 90 1000 10 20 30 40 50 60 70 80 90 100

19...07 hrs

07...19 22...01

1000 1500 2000 2196

07...19 hrs 19...22

19...07 01...04 04...07

07...10 10...13

13...16 16...19

10...13

07...19 a,

b,

i , kcal/kgo

i , kcal/kgo

Distribution ,F, %

τ

, h

Fig. 2. The distribution function of outdoor air enthalpy from October until March (Budapest, average of measured temperatures between 1964-1972) [10]

3 The physical and mathematical model

An air handling unit contains two main groups of elements: supply and exhaust units.

The main parts of an air handling unit: filter, heat recovery unit, pre-heater, re-heater, cooler, by-pass, adiabatic humidifier, fans [11,12]. In this article determination of heating energy consumption in winter time is published in the case of a few air handling units (AHUs) that are built up from the above-mentioned elements.

The general connecting diagram of AHUs is shown in Fig. 3. Without heat recovery and by-pass a classical fresh air supplied AHU come into being.

SH 1 F 1 SH 2

O

HR

V 2

V 1 F 2 AH RH

PH

R P M A

G'

S I G

BP

C

Fig. 2. The distribution function of outdoor air enthalpy from October until March (Budapest, average of measured temperatures between 1964-1972) [10]

adiabatic humidifier, fans [11, 12]. In this article determination of heating energy consumption in winter time is published in the case of a few air handling units (AHUs) that are built up from the above-mentioned elements.

The general connecting diagram of AHUs is shown in Fig. 3.

Without heat recovery and by-pass a classical fresh air supplied AHU comes into being.

Per. Pol. Mech. Eng.

62 László Kajtár/Miklós Kassai

(3)

Fig. 3. Connecting diagram of AHU

0 2 4 6 8 10 12 14 16 18 20 22 24

500

0

0 10 20 30 40 50 60 70 80 90 1000 10 20 30 40 50 60 70 80 90 100

19...07 hrs

07...19 22...01

1000 1500 2000 2196

07...19 hrs 19...22

19...07 01...04 04...07

07...10 10...13

13...16 16...19

10...13

07...19 a,

b, i , kcal/kgo

i , kcal/kgo

Distribution ,F, %

τ

, h

Fig. 2. The distribution function of outdoor air enthalpy from October until March (Budapest, average of measured temperatures between 1964-1972) [10]

3 The physical and mathematical model

An air handling unit contains two main groups of elements: supply and exhaust units.

The main parts of an air handling unit: filter, heat recovery unit, pre-heater, re-heater, cooler, by-pass, adiabatic humidifier, fans [11,12]. In this article determination of heating energy consumption in winter time is published in the case of a few air handling units (AHUs) that are built up from the above-mentioned elements.

The general connecting diagram of AHUs is shown in Fig. 3. Without heat recovery and by-pass a classical fresh air supplied AHU come into being.

SH 1 F 1 SH 2

O HR

V 2

F 2 RH V 1

PH AH

R P M A

G'

S I G

BP

C

Fig. 3. Connecting diagram of AHU The signs of Fig. 3 are the followings:

PH : pre-heater RH : re-heater C: cooler

AH : adiabatic humidifier

HR : heat recovery (cross flow heat exchanger(η=0,72)) V : ventilator

BP : by-pass (for air recirculation) F : filter

SH : shutter against the rain

Fig. 4 demonstrates the flowchart of four air handling units in Mollier enthalpy chart: a fresh air supplied AHU, with an air recirculation (BP) and adiabatic humidifier working AHU and both of them with heat recovery.

The signs of Fig. 3. are the followings:

PH : pre-heater RH : re-heater

C: cooler

AH : adiabatic humidifier

HR : heat recovery (cross flow heat exchanger (η=0,72)) V : ventilator

BP : by-pass (for air recirculation) F : filter

SH : shutter against the rain

Fig. 4. demonstrates the flowchart of four air handling units inMollier enthalpy chart:

a fresh air supplied AHU, with an air recirculation (BP) and adiabatic humidifier working AHU and both of them with heat recovery.

25 20 15

10 5 0 -5 -10 -15 -20

1,18

1,2 1,22

1,24

1,26 1,28 1,3 1,32 1,34 1,36 1,38 -10

0 0

10 20

3 40

50 60

750 1000 250 500

-500 0 -1000 -2000 -4000 -8000

Mollier h-x diagram total pressure 1000 mbar

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

1

2 4

0 6 8 10 12 14 16 18 20 22 24 26 28

-2

+2

h/ x ( kJ/kg )

Air temperature(°C)

0

Δx ΔhHR

ΔhRH

ΔhRoom

humidity x (g/kg)

Water vapor pressure p (mbar) R=P

O

S

G=I

A

Δh Δx M

G'

Fig. 4. Mollier h-x flowchart of AHU

Fig. 4. Mollierhxflowchart of AHU

3.1 Energy consumption of heaters:

QH =ρ·cpa· ˙V

tH

Z

20

F(to)dt; kJ/year (3) where:

ρ;kg/m3 air density

cpa;kJ/kg˚C specific heat capacity of air on fixed pressure V˙;m3/h air flow rate in heater

F(t0): distribution function of outdoor air temperature

tH; oC : air temperature after the heater

3.2 Energy consumption of fan:

Wf an =

Z V˙S·1pt f ηt f

dτ;kJ/year (4) where:

S;m3/h supply air flow rate delivered by fan 1Pt f;Pa the pressure loss of air handling unit ηt f; − the total efficiency of the fan

3.3 Energy consumption of pump:

Wpump =

Z V˙wat er·1pt p ηt p

dτ;kJ/year (5) where:

wat er;m3/h supply water flow rate delivered by pump 1Pt p;Pa lift of the pump

ηt p; − the total efficiency of the pump

Integration has to be calculated concerning the annual operation time. Peculiarities of AHUs working are continuous operation (0-24 hours) and intermittent operation (07-19 hours). During the energy consumption calculation of fan and pump integration can be determined easily thereby values of the working point data (V˙S,1Pt f ;V˙wat er,1Pt p)are taken into consideration as constants.

Analysis of energy consumption of air handling units based on probability theory 2008 52 2 63

(4)

3.4 Fresh air supplied air handling unit with heat recovery, pre-heater and re-heater (FAS-HR AHU)

Operation parameters of AHU with pre-heater and re-heater are shown on the distribution function of outdoor air temperature from October until March in Fig. 5. The signs of the figure are the followings:

F(t01): temperature distribution function after heat recovery,

tR ; oC : air temperature after the heat recovery which can be calculated by indoor and out- door air temperature and technological pa- rameters of heat recover unit,

tP H; oC : air temperature after the pre-heater, tR H; oC : air temperature after the re-heater, tS; oC : temperature of supply air, tI; oC : temperature of indoor air, tG; oC : temperature of outgoing air, tO; oC : temperature of outdoor air.

determined easily thereby values of the working point data ( V &

S

, Δ P

tf ;

V &

water

, Δ P

tp)

are taken into consideration as constants.

3.4. Fresh air supplied air handling unit with heat recovery, pre-heater and re- heater (FAS-HR AHU)

Operation parameters of AHU with pre-heater and re-heater are shown on the distribution function of outdoor air temperature from October until March in Fig. 5. The signs of the figure are the followings:

) ( t

01

F : temperature distribution function after heat recovery,

t

R

;

o

C : air temperature after the heat recovery which can be calculated by indoor and outdoor air temperature and technological parameters of heat recover unit,

t

PH

;

o

C : air temperature after the pre-heater, t

RH

;

o

C : air temperature after the re-heater, t

S

;

o

C : temperature of supply air,

t

I

;

o

C : temperature of indoor air, t

G

;

o

C : temperature of outgoing air, t

O

;

o

C : temperature of outdoor air.

0

PH RH

t = t 400

G [°C]

I tO

Distribution [%]

100 tPH tS

τtot

[hours]τ

F(t )O

= tRH

HR

tR

F(t )O1

-20

Fig. 5. Fresh air supplied air handling unit with heat recovery, pre-heater and re-heater in winter time (FAS AHU)

Fig. 5. Fresh air supplied air handling unit with heat recovery, pre-heater and re-heater in winter time (FAS AHU)

Energy consumption of pre-heater:

QP H =ρ·cpa· ˙V Z tP H

tR

F(to1)dt;kJ/year (6) Energy consumption of re-heater:

QR H =ρ·cpa· ˙V

tS

Z

tP H

F(to1)dt;kJ/year (7) The areas shown in Fig. 5 are proportional to energy consump- tion of the elements of air handling unit and the energy saving of heat recovery. In a similar way there is possibility to set up a physical and mathematical model of other air handling unit.

τt ot term which concerns to the 100% distribution has to be used for air handling units that are in continuous operation (0- 24 hours). Distributions that apply to half day have to be used for air handling units that are in intermittent operation (07-19 hours). The areas which are shown in Fig. 5 are proportional to energy consumption of the elements of air handling unit (PH, RH) and the energy saving of heat recovery (HR).

3.5 Air handling unit with pre-heater, air recirculation, adia- batic humidifier and re-heater (REC-AH AHU)

The order of the air handling elements is: PH+BP+AH+ RH

The air temperature after the adiabatic humidifier (tA)can be determined by winter air handling process on Mollier h-x chart.

Fig. 6 shows the energy consumption of air handling elements.

-20 0

RH t = t

400

[°C]

I G

tO

Distribution [%]

100 tPH

tS

τtot

τ

[hours] F(t )O PH

tA tM

a b

F(t )O1

Fig. 6. Air handling unit with pre-heater, by-pass, adiabatic humidifier and re-heater in winter time (REC-AH AHU)

The applied signs on Fig. 6 are the followings:

tA;˚C : air temperature after the adiabatic humidi- fier,

tM;˚C : air temperature after the air mixing.

Energy consumption of pre-heater:

QP H =ρ·cpa· ˙VP H·

tP H

Z

20

F(tO)dt ;kJ/year (8) where:

P H;m3/h : air flow rate in pre-heater

(5)

Energy consumption of re-heater:

QR H=ρ·cpa· ˙VR H·

tI

Z

tA

F(tO1)dt+(tS−tI) τt ot

2

 ;kJ/year (9) where:

R H;m3/h : air flow rate in re-heater

The calculation of heating energy consumption can be seen in the above-mentioned air handling units. Energetic analysis can be made in any air handling units in a similar manner with the help of the presented physical and mathematical methods and equations.

3.6 Energy consumption of analyzed air handling units The energy consumption of four air handling units were an- alyzed by the developed method. Energetic analysis was made in total heating season which takes from October until March and in the interest of exact energetic calculation was made par- ticularly in a daytime period (07-19 hours) and a nightly period (19-7 hours). The four analyzed air handling units can be seen below:

1 Fresh air supplied AHU (FAS AHU)

2 Fresh air supplied AHU with heat recovery (FAS-HR AHU) 3 AHU with air recirculation and adiabatic humidifier (REC-

AH AHU)

4 AHU with air recirculation and adiabatic humidifier and heat recovery (REC-AH-HR AHU)

The heating energy consumption of the air handling units can be seen in the daytime and nightly period in Fig. 7 and Fig. 8.

0 200000 400000 600000 800000 1000000 1200000 1400000 1600000 1800000 2000000

Air handling units

[MJ]

1.

2.

3.

4.

1: FAS AHU 2: FAS-HR AHU 3: REC-AH AHU 4: REC-AH-HR AHU

Fig. 7. Heating energy consumption in the daytime from October until March (07-19)

Operation of the AHUs can be seen in Fig. 4 and during the calculation the supply air flow rate was 20 000 m3/h.

4 Conclusions

Outdoor air parameters randomly vary from minute to minute.

These values can be regarded as a probability variable therefore

0 200000 400000 600000 800000 1000000 1200000 1400000 1600000 1800000 2000000

Air handling units

[MJ]

1.

2.

3.

4.

1: FAS AHU 2: FAS-HR AHU 3: REC-AH AHU 4: REC-AH-HR AHU

Fig. 8. Heating energy consumption at night from October until March (19- 07)

energy consumption of air handling units can be determined by probability theory model. In the interest of energetic evaluation of AHUs a probability theory model was developed. The phys- ical and mathematical model was made according to each air handling units.

The developed model is an appropriate method to determine energy consumption of air handling units in annual and in monthly period. Calculations can be made in reference to day- time operation (07-19 hours) and nightly operation (19-7 hours).

The mathematical model is based on the distribution functions of outdoor air. These distribution functions can be found in the literature. During our research temperature and enthalpy dis- tribution functions were used that are in reference to Budapest and were average of measured temperatures and enthalpy be- tween 1964-1972. In consequence of changes in the microcli- matic conditions outdoor air warming up can be noticed. In our department outdoor air parameters (temperature, humidity) are measured continuously. In this manner energetic analysis can be also made with the current outdoor air parameters.

On the basis of the new theoretical method it was possible to estimate the energy savings for each air handling unit to take into account heat recovery and heat recirculation. Daytime and nightly energy consumptions of the four air handling units have been analyzed by the developed methods from October until March. Results of energetic analysis are presented in Table 1.

Results show that energy savings are significant and applying of air-recirculation and heat recovery energy saving can be 79%.

Tab. 1. Rates of energy savings from October until March (00-24 hours)

AHU Energy saving

[MJ/year] [%]

1.FAS AHU 0 0

2.FAS-HR AHU 1 417 239 38 3.REC-AH AHU 2 102 541 57 4.REC-AH-HR AHU 2 916 135 79

Analysis of energy consumption of air handling units based on probability theory 2008 52 2 65

(6)

References

1 Kajtár L, Klímatechnikai rendszerek energetikai, gazdasági elemzése valószinüség-elméleti alapon, Budapest, 2005.

2 Kajtár L, Kassai M, Leveg˝okezel˝o központ energiafelhasználásának e- lemzése valószínüségelméleti módszerrel, Magyar Épületgépészet (2007), no. 4, 3-7.

3 Kajtár L, Gräff J, Kassai M,Központi légkondicionáló berendezések vil- lamos teljesítmény becslésére szolgáló közelít˝o számítási módszer, Gépészet 2008 konferencia CD., pp. 6.

4 Kajtár L, Kassai M,Klímatizált épületek energetikai elemzése, Magyar Épületgépészet (2008), no. 7-8, 3-7.

5 Kajtár L, Vörös Sz,Influence of Climate Change on Modelling of HVAC Systems, 2007. Portoroz, 2nd IASME/WSEAS International Conference on Energy & Environment, pp. 232-235.

6 Monostory I,Valószín˝uségelmélet és matematikai statisztika, M˝uegyetemi Kiadó, Budapest, 2002.

7 Kazuhiro F,Prediction of Energy Consumption by Using Weather Data, 2005 IASME/WSEAS International Conference on Energy, Environment, Ecosystems and sustainable development.

8 Kajtár L, Kassai M,Evaluation of energy demand of air-conditioning sys- tems based on probability theory, 6th IASME/WSEAS International Confer- ence on Heat transfer, Thermal engineering and Environment, 2008, pp. 266- 300.

9 Kajtár L, Vörös Sz,Risk-Based Modelling of Air-Conditioning System in Hungary, ROOMVENT 2004, 9th International Conference on Air. Book of Abstracts CD 6p., pp. 236-237.

10Kiss R,Légtechnikai adatok, M˝uszaki Kiadó, Budapest, 1980.

11Kajtár L,Klímatechnika – komfort – energetika, M˝uszaki Kiadványok:

F˝utés-, h˝utés- és klímatechnikaXI(2008), no. 171, 8-11.

12Zemljic A, Goricanec D, Krope J,The Recuperation of Waste Heat in the Air Conditioning Systems, The 3rd IASME/WSEAS International Confer- ence on Heat transfer, Thermal engineering and Environment, 2005, pp. 414- 419.

Hivatkozások

KAPCSOLÓDÓ DOKUMENTUMOK

Among the monitoring air handling data, the air temperature and relative humidity data of the inlet and outlet sections of the DX cooling coil, energy recovery unit, and outdoor

Drying curve of basil leaves dried by natural air-, hot-air- and vacuum drying Remark: NAD – natural air drying, HAD – hot-air drying, VD – vacuum drying The initial moisture content

The effects of outdoor air supply rate in an office on perceived air quality, sick building syndrome (SBS) symptoms and productivity.. What does the scientific literature tell us

Respondents who have demonstrated high level of awareness about the energy consumption cots in the company (“Electricity consumption has a significant share in the total cost

2.2 Contribution of air transport to sustainable development Air transport contributes to sustainable development signifi- cantly through the promotion of international

— Energy consumption, air pollution and production structure, Uitg.: Centraal Bureau voor de Stutistlek..

In the example below, we intend to show how entropy production rate enables the comparison of recovery performance of two different models of counterflow air to air heat

The article consists of analysis of existing and planned air pollution from ships control and prevention tools such Marpol 73/78 Annex VI, Energy Efficiency Design Index,