DESIGN OF INDIRECT-TRANSFER (RUN-AROUND-COILSYSTEM)

HEAT EXCHANGERS G. VERES and S. BALIKO Institute of Heat- and Systems-Engineering,

Technical University, H-1521 Budapest Received December 15, 1983 Presented by Prof. Dr. I. Szab6

Summary

Heat transfer of gases at atmospheric pressure results in low heat transfer rates per unit of surface area. In addition to some practical considerations, it is the demand on decreasing surface areas that has created the possibility of a wide-spread industrial application for indirect-transfer heat exchangers. In this paper, a heat transfer design theory of indirect-transfer heat exchangers is presented. Comparative evaluation is made for heat engineering parameters of different heat exchanger types with a particular regard to the case of heat exchangers with heat pipes.

It is well known that for gases at atmospheric pressure flowing over a solid surface, the heat transfer coefficients are very small and, consequently, the surface area necessary for the heat transfer is considerably larger to that of heat exchangers with liquid media. If one of the two fluids is a low pressure gas, the latter generally flows over the outside surface of heat transfer tubes and the low heat transfer coefficient is compensated by an increased outside surface area, that is, a finned outside surface.

Increasing the inner surface area of tubes is a difficult task and is never possible to such a degree as in the case of the outside surface. Therefore, heat exchangers with two gas fluids at low pressures have usually larger dimensions than liquid-flow exchangers of the same performance.

In addition to several practical considerations, particularly the layout adventages due to an easy handling of fluids, it is the demand on decreasing surface areas that has created the possibility of a wide-spread industrial application for indirect-transfer heat exchangers.

The indirect-transfer heat exchanger is essentially a system of direct-type heat exchangers and consists of, as shown in Fig. 1, a "hot" heat exchanger with a surface area F 1 and a "cold" one with a surface area F 2'

In the hot exchanger, the cooling of hot fluid takes place with high heat transfer coefficients by a fluid of flow-stream capacity rate

w;,

and this fluid

(2)

280 G. VERES S. BAL/KO

expansion tank

cold gas tlin ~1

b

tv2 Wv t10ut

lZol1 Wv t vl

Fl

I-.::::::=-=-=:::,..

t..=-_=:..lF. W2 t

- or 2 2in

~-:=,.J~

W1 tlin Wv \

hot gas coupling fluid Fig. 1

with the same thennal capacitance J.V;, is applied for heating the cold fluid in the cold heat exchanger. The coupling fluid is circulated by a pump, however, the overall arrangement in a given case might allow the application of free circulation.

In steady operation, the two exchangers have the same performance thus the coupling fluid is heated up in the hot exchanger in the same degree as it is cooled down in the cold one. Hence, the temperatures tvl and tv2 will approach to constant values determined by the values of heat transfer areas, overall thermal conductances and thermal capacitances.

If the thermal conductance J.V;, is known, the dimensionless temperature change of the coupling fluid can be calculated since it is independent of actual temperature values:

=

9

(k

1

F

1 J.V;, )

vl W' W

v 1

Supposing both exchangers are of a simple counterflow arrangement,

and

_kiFi(l_ Wv)

1-e Wv Wi 9vi = --W--k-.F-.-( -w-v-) ,

1 --.£.e-wv' l-Wi

lti

9vi= ---1-' 1 l+k.y

I I

lti=J.V;,=W

W

where i = 1 refers to the hot exchanger and i = 2 to the cold one.

(1)

(2)

(3)

INDIRECT-TRANSFER HEAT EXCHANGERS 281

The performance of each of the exchangers is given by

Q

=

W1 8v1 (t 1 be - t lkd

=

w,,(tv2 - tvd

=

W2 (t2ki - t2 be), (3) although, the performance may be written also employing the dimensionless temperature of the coupling fluid as

(4)

Q=Wv8v2(tv2-t2be) (5)

Equations (3), (4) and (5) yield the performance as a function ofthe known parameters:

Applying the symbol Wk to the smaller thermal capacitance and introducing this into the performance equation,

w,

k -

w"

~ (

Q= 1 1 t1be-t2be)=~ P(tlbe-t2be) - + - - 1

8v1 8v2

(6)

where P is the effectiveness of the indirect-transfer heat exchanger:

w"

W1

P=

(7)

It is often more convenient to employ, instead of the magnitudes 8v1 and 8v2 concerning the coupling fluid, the dimensionless temperature differences 81 and 82 concerning the fluid to be cooled and the fluid to be heated, respectively.

Since the thermal capacitances are known:

(4)

282 G. VERES S. BALlK6

one obtains for '1'

1

'1'= (8)

1

The outlet temperatures can be calculated from the performance Q as follows:

where

t I ki

=

t I be -

W Q

I

(9)

(10)

The extremes of the coupling fluid temperature are given by Eqs (4) and (5):

Q Q

tvl =tlbe - W,9 = t lbe - w,,9

v vi 1 I

(11)

(12) In the special case when changes in phase take place both in the hot and the cold fluid, i.e. both WI and W2 start indefinitely high, then ,9vI

=

<PI and ,9v2

=

iP2, therefore

' 1 ' = - - - - -

~+_1 1 iP I iP2

(13)

and where

and

(5)

INDIRECT-TRANSFER HEAT EXCHANGERS

The temperatures of the coupling fluid will be Q

w"Wl '

tv2=t2be+

w"

QW

2

;

283

(14)

(15) The value of IJI depends on the ratio of hot and cold fl~id thermal capacitances. In most cases 831/8W1 < 1 and 832/8W2 < 1, therefore, an investigation of Eq. (8) shows that (with the above restrictions) the function IJI has a minimum at Wt/W2 = 1, as shown in Fig. 2.

IJI is a function also of the coupling fluid thermal capacitance. Very low values of

w"

result in 3d ~ 3v2 ~ 1 and so Eq. (7) leads to

lim IJI =0 (16)

wv .... o

When

w"

increases infinitely, the ratios w,,/W1 and w,,/W2 start indefinitely high while the dimensionless temperature differences approach the Bosnjakovic number W (or effectiveness) of heat exchangers with a change of phase in one of the fluids. Consequently, from Eq. (8):

IJI 0 = lim IJI = (17)

Wv-+C()

The curve 1JI(w,,), characterized by the limits Wv=O and Wv-tCX), after an initial raise as far as a maximum value, descends approaching the value given by Eq. (17) as shown in Fig. 3 where IJI is presented as a function of the non- dimensional parameter x

=

W1/W2 for different thermal capacitance ratios a

=WdW2 • .

The function has no maximum value at any finite

w"

if W1 = W2-tCX).

The special condition

w"

- t CX) can be established by a heat pipe as shown in Fig. 4.

The temperature of the two-phase fluid in the heat pipe can be calculated from the equality of performances on the two (hot and cold) sides as follows

(6)

284

cold

W2

t2 in

If 0.6 0.5 0.4 0.3 0.2 0.1

0.6 If 0.5

0.4 0.3

0.2 0.1

gas

couplin 9 fiuid

G. VERES S. BAL/KO

02

F2

F2

\

~.5

)%c

0.5 1.0 1.5 2.0 o Fig. 2

2.0 0=0.5

· _ - - - - 1 . 5

x = WV

W2

1.0

0.6 1.0 1.4 1.8 2.0 x Fig. 3

t 2 out

ts tlout

t'''~

t2ou1

t 2 in

F Fig. 4

(7)

INDIRECT-TRANSFER HEAT EXCHANGERS

Q= Wl 1[>1 (tlbe-tS)= W21[>2 (ts-t 2be ) from which ts can be expressed as

Wl cl> 1

W

~tlbe+t2be

t

=

2 2

s Wl cl> 1 1

- - +

W2 cl>2

Let us suppose that Wl ~ W2 and substitute Eq. (19) into (18), then Q= Wl 1[>1 (tl be-ts)= 1 1 W

l (t lbe - t2be)=

- + - -

cl> 1 W2 cl>2

Similarly, in the case of W2 ~ W1 ,

Q = W2 tp 0 (t lbe t 2 be);

285

(18)

(19)

(20)

(21) All this goes to show that heat pipe actually is a special case of indirect- transfer heat exchangers; it is obtained by the restriction Wv~oo.

A single heat pipe or a series of heat pipesl can be used only if the outlet temperature of the hot fluid is higher to that of the cold one. However, even in this case, the performance of a heat pipe is smaller to that obtainable by an indirect-transfer heat exchanger with the same value of (kF). In order to eliminate this disadvantage, a set of heat pipes is usually applied in an equipment which are coupled in series.

A heat exchanger consisting of two heat pipes is shown in Fig. 5. Outlet temperatures and temperature values of the coupling fluid can be obtained, after setting up energy balances and heat transfer formulas, from the following system of linear equations with six unknowns:

3

Wl (tlbe-ti)= W2 (t2ki- ti) t 1 be - t1' = 1[>11 (t 1 be - tsl )

t2ki -t!=cl>12(tSl ti) W1 (t1' tlkJ= W2 (t 2 - t 2be )

t1' - tl ki

=

cl>21 (t1' - ts2 ) t! - t 2 be = cl> 22 (t s2 - t 2 be)

(22)

(8)

286 G. VERES S. B.4L1KO

cold gas

Fig. 5 where

i= 1, 2;

The total heat transfer area is

t lout

""-1"-"""

F

j=1,2.

(23) If more than two heat pipes are used· and coupled in series, a similar system oflinear equations is obtained. The resulting P number of the serially- coupled heat pipes can be calculated from the outlet temperatures:

tkbe - tHi tkbe-tnbe

(24) where the index k refers to the fluid with the smaller thermal capacitance while n refers to the other one.

Let us consider now the marginal case where an infinity of heat pipes is coupled in series. Denoting as Fk dx the surface area of an infinitesimal heat pipe in a section dx taken in the flow direction, a thermodynamic balance results in

(25)

that is to say

(26) and the latter yields

(27)

(9)

INDIRECT-TRANSFER HEAT EXCHANGERS 287

The transported energy changes the hot and cold fluid temperatures in inverse ratio to the thermal capacitances:

(28)

Eqs (25) and (27) yield

dtk kkFk

- = - - - ( t k - t )

dx

Wk

S

(29)

(The negative sign is necessary because, at a counterflow arrangement, both tk and tn decrease in the direction of the

+

x axis.)

Summing up the two equations and substituting Eq. (27), one obtains

Substitution of the boundary conditions gives the results 1 e- fJ

tkki=tkbe

m

(tkbe-tnbe)=

1-_ k e-fJ

w"

=tkbe- 'l'(tkbe-tnbe)

As for the heat exchanger performance, Q=

Wk

'l'(tkbe-tnbe) wliere

3*

(31) (32)

(33)

(34)

(10)

288 G. VERES S. RALlKO

and

1-

~

f3 --

kkFk

w,.

(35)

~ 1 kkFk

+--

knFn

If kkF k = knF n = k

~

and F is the total installed heat transfer area, then an evaluation of Eq. (34) shows that, for equal unit overall thermal conductances, a heat pipe heat exchanger requires four times the surface area of a pure counterflow exchanger to obtain the same performance, that is,

'I' (4F) = cP counterflow(F) ;

A summary of indirect-transfer heat exchanger calculating formulas is given in Table 1. One can see that the performance of each of the exchanger types is proportional to some nondimensional factor denoted as 'I'. This factor 'I' can always be calculated from the effectiveness of the given unit and the ratios of thermal capacitances; it is analogous to the Bosnjakovic number cP of direct-transfer heat exchangers.

For equal overall conductances, 'I' is the highest possible for direct- transfer, pure counterflow exchangers. ('I'

=

cP) A considerably lower 'I' value can be obtained employing a heat pipe, nevertheless, this value can be improved by serially coupled heat pipes.

For an exchanger operating with liquid coupling fluid, 'I' is a function of the thermal capacitance of the latter but it can be usually adjusted, by a proper choice of

w."

in between the 'I' values of an exchanger with a single heat pipe and that with an infinity of heat pipes (Fig. 6).

However, the above comparison is solely of theoretical importance since unit overall thermal conductances (k) in indirect-transfer exchangers are, in general, higher to those in direct-transfer exchangers. Consider, for example, the case of a counterflow, gas-to-gas exchanger where the heat transfer coefficients inside and outside the tubes are equally IXb

=

IXk

=

50 W

1m2,

K. Let the heat transfer tube be finned at a ratio FklFb= 10 of surface areas. The overall thermal conductance for this heat exchanger is approximately

1 2

k= 10 1 =4.545 W/m ,K.

- + -

IXb IXk

If, on the other hand, a heat transfer coefficient IXb

=

3000 W

fm

2, K is obtainable by using a liquid (e.g. water) coupling fluid, the unit overall thermal

(11)

'1' factor

Total heat transfer area Exchanger performance Outlet temperatures

Table 1

Summary of Indirect-Transfer Heat Exchanger Correlations (W1 < W2 ) Pure counterflow

exchanger without coupling fluid

hi" w\

I-e-w.('--w.)

n - kF 11") 'P="l- w, --'('-w,

I - - e n, W2

F=F

o<w.,<W

(liquid coupling fluid)

' 1 ' = - - - -

I W, W,

+---

,9, W2.92 w.,

( k,F, W,)

.9,=.9, - . -

W, w.,

(k2F2 W2) tJ2=,92 - , -

W2 10/;,

F=F1 +F2 Q= W, '1'(llhe-12hc) I I kl =/, he - 'P(t, hc- 12he)

W1

12kl =12he+ - '1'(11 hc- I 2h.) W2

Indirect-transfer exchangers

'I'

w.,-+oo (heat pipe)

+ - -W,

</', W2 <1>2

klFI

<1>, = l-e---W;-

k2F2

</'2 = l-e---W;-

1'=1', +F2

Infinite series of heat pipes

I-e-P

'1'= W'_p

I - - e W2

kiF,

1 (

W,)

{J=

--w;- -kiF,

1-

W

1 + - - 2

k2F2

F=F, +F2

;; ~

~ ";'I

;;; ;,..

~ [;;

:J: t

-!

~ ~

'"

~

'"

'"

'v 00

'"

(12)

290 G. VERES S. BAL/KO

k = 30W/m2!"C

W1 =1.0kW/oC W2 = 2.0kW/oC It' 1.0 counterflow heat exchanger

OB

0.6 0.4 0.2

an infinity of heat pipes single heat pipe

0.5 1.0 1.5 2.0 2.5 kW/"C W

Fig. 6

Table 2

Comparing of Exchanger Type Performances on the strength of a Numerical Example

Unit overall thermal conductance, W/rn2, K If' factor

Exchanger performance, W Related performance, per cent

Counterflow exchanger Indirect-transfer without coupling exchanger

fluid Cw,. = 1300 W)

4.545 0.3379 28724 100

W,=l000W/K W2=2000W/K

42.857 0.5863 49836 173.5

Single heat Infinite series pipe of heat pipes

47.619 0.5493 46691 162.6

47.619 0.6193 52641 183.3

conductance will be k =42.857 W/m2, K, furthermore, in case of employing a heat pipe, a heat transfer coefficient as high as ab = 10000 W /m2, K is attainable resulting in k=47.619 W/m2, K. These values already yield a better base for comparings.

Using the above conductivity values, Table 2 contains performance data for the different possible realizations of a heat exchanger with 100m2 total heat transfer area.

It is clearly indicated by the table that, for the case presented above, the least performance of all is given by the direct-type counterflow exchanger and that a performance higher by 60-80 per cent to this value can be obtained when a coupling fluid is used.

(13)

INDIRECT-TRANSFER HEAT EXCHANGERS 291

The economic advantage of employing indirect transfer heat exchangers is a conclusion of the above-mentioned train of thoughts. Namely, if the savings deriving from the decrease in surfaces and the layout advantages cover the energy costs connected with assembling and installation, employing of the device is economical.

Nomenclature Letter Symbols

a

=

W1/W2 - Dimensionless parameter F - Heat transfer area, m2

k - Unit overall thermal conductance, W/m2, K

Q -

Heat transfer rate, W or kW t - Temperature, QC or K

W Flow-stream capacity rate, W/K or kW/K x =

w,,/W

2 - Dimensionless parameter

8 - Dimensionless outlet temperature

<f>

=

(tkbe - tkki)/(tkbe - t nbe ) - Bosnjakovic number

'P - Effectiveness of indirect-transfer exchanger

Subscripts

be - Inlet

ki - Outlet

k - Refers to the fluid with the smaller thermal capacitance n - Refers to the fluid with the larger thermal capacitance

s - Saturation

v - Coupling fluid

Note 1

In thermodynamic sense, a single heat pipe or a series of heat pipes in a system is the complex of heat pipes operating at the same temperature and, consequently, containing the fluid at the same saturation temperature.

Gergely VERES }

D S' d B ' H-1521 Budapest r. an or ALlKO

Hivatkozások

KAPCSOLÓDÓ DOKUMENTUMOK

Since any pair of points can be joined by a (finite) chain of circles with radius r it follows that f is a constant function. Especially, the constant must be zero.. Gottschalk,

Using primers previously described the differentiation of Mycoplasma strains was not possible and MI 4229 was amplified. While we used primers performed in this study

This article is devoted to the solution of the thermal field of a particle for Bi &gt; 0 with an ideal spherical shape and the behavior of the temperature in the fluid phase

The method discussed is for a standard diver, gas volume 0-5 μ,Ι, liquid charge 0· 6 μ,Ι. I t is easy to charge divers with less than 0· 6 μΐ of liquid, and indeed in most of

The localization of enzyme activity by the present method implies that a satisfactory contrast is obtained between stained and unstained regions of the film, and that relatively

The mononuclear phagocytes isolated from carrageenan- induced granulomas in mice by the technique described herein exhibit many of the characteristics of elicited populations of

A heat flow network model will be applied as thermal part model, and a model based on the displacement method as mechanical part model2. Coupling model conditions will

The present paper reports on the results obtained in the determination of the total biogen amine, histamine and tiramine content of Hungarian wines.. The alkalized wine sample